Multi-machine transient modelling of wind farms: An essential approach to the study of fault conditions in the distribution network.
- Autoría:
- I. Zubia, J. X. Ostolaza, A. Susperregui, y J. J. Ugartemendia.
- Año:
- 2012
- Revista:
- Applied Energy
- Volumen:
- 89(1)
- Página de inicio - Página de fin:
- 421 - 429
- Descripción:
-
Abstract:
This paper reports the study carried out to asses the dynamic behaviour of a real wind farm during fault conditions in the distribution network. The objective is to obtain a transient model valuable for all kinds of operational conditions. The paper begins with a detailed modelling of the distribution network between the wind farm common busbar and the point of common coupling with the HV transmission system, for all types of short-circuits. The state-space network model, together with the electromagnetic transient model of each wind generator, configure a multi-machine wind farm model, with 572 state variables. Simulation results prove that multi-machine modelling is mandatory in order to tackle the wind farm contribution to symmetric and asymmetric short-circuits.